The Transfer Operation

10/05/2021

The main and transfer bus arrangement does not provide bus-bar redundancy, the transfer bus is a mechanism to ‘transfer’ the operation of a circuit to a transfer breaker, releasing the circuit breaker for maintenance or repair to be done. But if the main bus-bar fails, we run out of system.

The safety criteria for this transfer operation are:

  • Never have a section energized if it is not necessary.
  • The connection operation between energized and non-energized sections must always be carried out with a breaker operation (not with a disconnector operation)

The disconnector can be used if the above is not feasible only to join an energized section with a short de-energized section, for example a connection between disconnector and its circuit breaker, but not a transfer bus.

This disconnector operation will generate a low intensity electric arc in the final closing phase of the disconnector.

For inquiries related to the im3 Classroom 2021 program, please contact through classroom@ingenieros-im3.com



logoim3
Privacy Overview

This website uses cookies so that we can provide you with the best user experience possible. Cookie information is stored in your browser and performs functions such as recognising you when you return to our website and helping our team to understand which sections of the website you find most interesting and useful.